Dry Room Humidity Measurement

By October 13, 2026News

Dewpoint, RH or ppm(v)?

Dry room humidity measurement can be expressed in three common ways: dew point, relative humidity (RH) and parts per million by volume, written ppm(v). All three describe the moisture condition of a gas but they are not equally useful in a lithium-ion battery dry room.

Specifications may use different units. Some process or chemistry limits are expressed in ppm(v), while plant and zone targets are often expressed as dew point. Here is what each unit means, how the values relate and which measurement is most useful in practice.

What Each Unit Measures

Above 0 °C, dew point is the temperature at which a gas, when cooled at constant pressure and water vapour content, becomes saturated with respect to liquid water and condensation can begin. A lower dew point means less water vapour.

If the moisture content remains constant, dew point remains approximately constant even when room temperature changes. This makes it useful as a control and specification parameter for dry rooms.

Below 0 °C, the reference may be the saturation curve over ice, in which case the value is commonly called frost point. Many instruments use “dew point” as a general label for sub-zero measurements, so it is worth checking which reference curve is being used. At very low moisture levels, dew point and frost point can differ by several degrees.

Relative humidity is the ratio of the actual water vapour partial pressure to the saturation vapour pressure at the current air temperature, expressed as a percentage. Because saturation vapour pressure changes with temperature, the same moisture content produces a different RH at 20 °C and 25 °C. Specialist RH instruments can measure very low values, but RH becomes a small, temperature sensitive number in a dry room. Dew point or ppm(v) is usually more practical for specifying and comparing very dry atmospheres.

ppm(v) expresses the water vapour mole fraction: the number of water vapour molecules per million molecules of the gas mixture. At a specified total pressure, it can be converted to dew point or frost point. The conversion depends on pressure and on whether the calculation uses the ice or liquid water saturation curve.

How the Three Units Relate

At approximately 101.325 kPa, the following approximate relationships apply. The sub-zero values use the ice saturation reference and RH is calculated at an air temperature of 20 °C.

Frost Point (°C) Approx. ppm(v) Approx. RH at 20 °C
-30 °C  375 1.6%
-40 °C 127 0.55%
-45 °C 71 0.31%
-50 °C 39 0.17%
-60 °C 10.7 0.05%

In the table above, frost point is shown for sub-zero conditions; many instruments and specifications label these values as dew point.

Values may vary slightly with the vapour pressure equations and reference convention used.

At approximately 1 atm, 100 ppm(v) corresponds to about −42 °C when calculated using the ice saturation curve. The exact temperature depends on pressure and on whether the ice or liquid water reference is used.

The RH column illustrates one limitation of using RH in a very dry room. The range from −40 °C to −60 °C corresponds to less than 1% RH at 20 °C. An instrument that cannot resolve small fractions of a percent may struggle to distinguish between different dry room specifications.

Which Unit Should a Dry Room Use?

For most dry room control and comparison, specify and monitor dew point.

Dew point remains a meaningful representation of moisture content when room temperature changes and it can be converted to ppm(v) when a process limit is quoted that way. RH can still be useful in other environmental and clean room applications, but it is generally less convenient as the primary specification for an ultra dry, battery manufacturing environment.

Two details should be stated in any specification:

  • Whether sub-zero values use the ice or supercooled liquid reference
  • The total pressure at which ppm(v) is specified or calculated

Dry Room Humidity Measurement in Practice

Measure dew point continuously at representative locations in each zone, not only at the dehumidifier supply. Fixed dewpoint transmitters can provide continuous readings in selected zones, while a portable hygrometer can help an engineer verify fixed instruments during commissioning, maintenance and troubleshooting.

Sampling method, pressure, sensor location and stabilisation time should be considered when comparing readings from different instruments.

We explain why a single supply reading may not be enough in Why Measuring Dewpoint at the Dehumidifier Isn’t Enough.

Our application note Dewpoint Measurement in Lithium-Ion Battery Manufacture covers the moisture mechanisms and measurement locations in more detail.

If you would like help choosing dewpoint instruments for your dry room, please get in touch with our team.